Ask an operator what they expect to worry about and they will say equipment, or rent, or staffing. Nobody says grease interceptor. Then they take a second-generation space with an undersized one buried under the slab, and it becomes the most expensive plumbing decision of the project.
Two sets of rules govern it, and they answer different questions. The Ontario Building Code says when you need an interceptor and how it is selected, sized and installed. Your municipality’s sewer-use by-law says how you maintain it, how often it is pumped, and what records you keep. The first is the same everywhere in Ontario. The second is not.
When the Building Code requires one
Permits applied for now fall under the 2024 Building Code, O. Reg. 163/24, in force since January 1, 2025. Its plumbing rules are in Division B, Part 7, and the one that matters is Article 7.4.4.3:
Except for suites of residential occupancy, where a fixture discharges sewage that includes fats, oils or grease and is located in an area where food is cooked, processed or prepared, it shall discharge through a grease interceptor.
That covers almost every commercial kitchen that cooks, and plenty that only prepare. A butcher’s cutting room, a bakery’s pot sink and a café’s three-compartment sink are all fixtures in an area where food is processed or prepared. Which fixtures connect to the interceptor, and which must not, is a design decision the plan examiner checks.
Whether a lighter concept escapes it — a coffee bar with no cooking, a juice bar — depends on what actually goes down its drains, not on what the business is called. Ask before you assume.
How it is sized and where it goes
The Code does not leave sizing to judgement. Article 7.2.3.2 requires grease interceptors to be selected and installed in conformance with CSA B481.0 (material, design and construction) and CSA B481.3 (sizing, selection, location and installation). The size comes from the fixtures that drain to it and the flow they produce, which is why the calculation belongs in the permit drawings. A missing interceptor sizing calculation is one of the standard reasons a plan review comes back with comments.
Article 7.1.3.2 adds that every interceptor has to be located so it is readily accessible for use, cleaning and maintenance. In practice the location is where the money is:
- Back-of-house, near the fixtures is usually best, and it consumes floor area you were planning to use for something else.
- Under a slab in the dining room can be made to work and is miserable to service.
- Outside, in the parking area, suits a large in-ground unit but needs the landlord’s consent and a route for the pump truck.
- Retrofitting a wrong-sized or wrong-placed unit means breaking concrete, re-running drainage and restoring the slab, with the schedule that comes with it.
The menu changes the answer. Adding a fryer to a concept that was going to be sandwiches changes the grease load, and with it the interceptor and the hood.
What each city’s sewer-use by-law adds
Each by-law below sits on top of the Building Code requirement and adds its own operating rules.
| City | By-law | What it requires |
|---|---|---|
| Kitchener, Waterloo, Cambridge | Region of Waterloo Sewer Use By-law 21-036, s. 16 | Every operator of a restaurant or other commercial building where food is cooked, processed or prepared installs and maintains an interceptor to Building Code requirements |
| Guelph | Sewer Use By-law (2024)-20911, s. 9.1.1 | Install, operate and maintain an interceptor; building permit first; OBC and CAN/CSA B481; clean before solids reach 25%; post the maintenance requirements beside it; keep proof for two years |
| Toronto | Municipal Code Chapter 681, § 681-10B | Install to the Building Code and maintain it to the Food Service Establishment Environmental Code of Practice; the City can order a new one if an existing one harms the sewer |
| Mississauga, Brampton (Peel Region) | Wastewater By-law 53-2010 | Any commercial premises that may discharge fats, oils or grease installs, operates and maintains an interceptor to the Building Code Act |
| Vaughan, Markham and the rest of York Region | York Region Sewer Use Bylaw 2021-102, Part 14 | Restaurants keep grease out of the sewer; interceptor to the Building Code and CAN/CSA B481; clean before solids reach 25% and at least every four weeks; post the maintenance requirements; keep proof for two years |
| Markham | Sewer Use By-law 2023-150, s. 14 | Every food sector establishment uses an interceptor; pot, pan and dish sinks, cooking equipment drains and hood drains connect to it; building permit to install or replace; clean at least every four weeks; two years of records |
| Oakville, Burlington (Halton Region) | By-law 184-95, ss. 27–28, and By-law 2-03, s. 14(3) | Interceptors at restaurants and food preparation establishments, at the owner’s or occupant’s expense, kept in continuously efficient operation; accessible for cleaning; 24 months of maintenance records |
| Oshawa and the rest of Durham Region | Sewer Use By-law 55-2013, ss. 17–21 | Every restaurant installs, operates and maintains an interceptor to CAN/CSA B481; clean before solids reach 25%; maintenance record on request; one year of clean-out proof |
| Hamilton | Sewer Use By-law 14-090, s. 7 | An officer can require a grease control device within six months of written notice, or on a risk schedule where a restaurant of 30 or more seats is first priority; maintain to the manufacturer or CSA B481; three years of records |
| London | Waste Discharge By-law WM-16, ss. 6.1–6.2 | The City Engineer may require a commercial premises to install and maintain a device that keeps grease out of the sewer; proof of maintenance on request |
Each by-law also caps how much animal or vegetable fat, oil and grease the sewer will accept: 100 mg/L in Waterloo Region and London, and 150 mg/L in Toronto, Peel, York Region, Markham, Halton, Durham and Hamilton. Guelph sets its limit in its own schedule, and Vaughan has its own Sewer Use By-law, 025-2024, on top of York Region’s. A working interceptor is how a kitchen stays under it.
A few things in that table are worth reading twice.
Waterloo Region (Kitchener, Waterloo and Cambridge) regulates it once, for all three cities. The Region’s guidance asks businesses to maintain the interceptor to the manufacturer’s instructions and CAN/CSA B481, to keep maintenance records — date, who did the work, repairs, the volumes of water, solids and grease found, and the disposal method — and says businesses discharging fats, oils and grease must apply for a permit under the by-law.
Toronto sets the most specific schedule in the province. Its Code of Practice requires a grease interceptor to be serviced every four weeks, or before the grease and solids together reach 25 per cent of its liquid volume, or before the fats, oils and grease exceed its rated capacity — whichever comes first. The City can allow up to eight weeks if your records show the unit stays under 25 per cent in the first four. Servicing records have to be kept at the establishment for at least seven years.
Peel Region writes its clause for “industrial” premises, but the by-law defines industrial to include commerce, trade and business, so a restaurant in Mississauga is inside it.
York Region says on its own pages that every restaurant must have a grease interceptor, and Markham writes a second, more detailed by-law on top: it names the fixtures that must drain to the interceptor and requires a City building permit to install or replace one.
London and Hamilton write their by-laws so the device becomes a requirement when the City asks for it: London’s City Engineer, or a Hamilton officer by written notice or on its risk schedule. The Building Code requirement in Article 7.4.4.3 applies to the plumbing regardless.
Maintenance is an operating cost, for the life of the lease
An interceptor is a service contract on a schedule. Skip it and you get backups, odour, a failed inspection and a by-law problem, and the by-laws give the municipality the right to ask for your records. Budget it from day one, the same way you budget hood cleaning.
Two rules hold everywhere we work. Keep the records, because the clean-out receipt is the only proof the work was done. And do not use enzymes, bacteria, solvents or hot water to push grease through: Guelph’s by-law prohibits it outright, and Toronto and the Region of Waterloo say the same. The grease only breaks up for a while and sets again further down the line.
The second-generation trap
Second-generation spaces are usually the right choice, because they come with services already in place. But “there is already one” is not the same as “there is a suitable one”. Before you sign, establish:
- Is there one, and exactly where? Located, not described.
- What size is it, and what was it sized for? The previous tenant’s menu may have been far lighter than yours.
- When was it last serviced, and is there a record? A neglected interceptor is a maintenance problem you inherit.
- Can a pump truck reach it? Accessibility is a Code requirement, not a convenience.
- Who owns it under the lease? In a plaza with several food tenants on one interceptor, the servicing cost and the capacity are shared, and the split is whatever the leases say.
Get it into the lease
Before signing, get in writing whether an interceptor exists and is sized for your intended use, who pays if it has to be upsized or relocated for you, who services it and how a shared one is split, and what condition it must be left in at the end of the term. The middle two are the ones that cost money later.
When we review a unit, the interceptor is on the checklist beside the gas service and the roof access, for the same reason: it is one of a small number of things that can turn an affordable second-generation space into a slab-breaking project. The drawings it belongs in are part of design and drawings, and how it fits with the sinks and the dish machine is in the dish area.
Sources
- Building Code, O. Reg. 163/24, ss. 2–4 (transition and commencement): ontario.ca/laws/regulation/r24163
- 2024 Building Code Compendium, Division B, Part 7, Articles 7.1.3.2, 7.2.3.2 and 7.4.4.3: ontario.ca/document/2024-building-code-compendium/part-7-plumbing
- Region of Waterloo Sewer Use By-law 21-036, s. 16 and Table 1: regionofwaterloo.ca, and the Region’s guidance for businesses discharging fats, oils and grease: Protect your pipes
- City of Guelph Sewer Use By-law (2024)-20911, s. 9.1.1: guelph.ca
- Toronto Municipal Code Chapter 681, Sewers, §§ 681-10B and 681-14.3: toronto.ca, and the Code of Practice pages on interceptor maintenance and installation
- Region of Peel Wastewater By-law 53-2010, definitions, Part 14 and Table 1: peelregion.ca
- City of London Waste Discharge By-law WM-16, ss. 3.3, 6.1 and 6.2: london.ca
- York Region Sewer Use Bylaw 2021-102, Part 14 and Schedule A: york.ca, and the Region’s sewer use permits page
- City of Markham Sewer Use By-law 2023-150, s. 14 and Schedule A: markham.ca
- City of Vaughan Sewer Use By-law 025-2024: vaughan.ca
- Halton Region Wastewater System By-law 184-95, ss. 27–28: halton.ca, and By-law 2-03, s. 14(3) and Table 1: halton.ca
- Durham Region Sewer Use By-law 55-2013, ss. 17–23 and Table 1: durham.ca
- City of Hamilton Sewer Use By-law 14-090, s. 7, Schedules B and E (office consolidation): hamilton.ca
All checked November 8, 2026. The authority having jurisdiction decides any specific project.